GENERAL FEATURES |
Type | Line-Interactive (VI) |
Phases (IN-OUT) | 1-1 |
Form Factor | Rack, Counter-Mountable, Tower |
Rack Units [U] | 2U |
Power Capacity | 1000VA / 900W |
Output Power Factor | 0.90 |
INPUT |
Input Voltage Range | 165-290 VAC |
Frequency Range | 45Hz – 65Hz |
OUTPUT |
Waveform | Pure Sine Wave |
Nominal Output Voltage | 230 VAC |
THDv | ≤3% @ 100% linear load, ≤5% @ 100% non-linear load |
Voltage Regulation (Battery Mode) | ±10% |
Frequency (Battery Mode) | ±1% |
INPUT & OUTPUT CONNECTORS |
Input Connector | C14 |
Output Type | IEC |
IEC C13 | 8 |
TECHNICAL DETAILS |
LINE Mode Efficiency [%] (Full Load) | 98.8 |
Battery Mode Efficiency [%] (Full Load) | 82.3 |
Transfer Time (AC / Line Mode to Battery Mode) [ms] | 2-6ms typical (10ms max) |
Additional Features | LCD Display, Generator Compatible, EPO – Emergency Power Off, HID – Human Interface Device, AVR – Automatic Voltage Regulator, Battery Pack Available, Cold-Start Function, Circuit Breaker Reset, Potential Equalization Screw, Programmable Segment Available, Overload Recovery, Off-Mode Charging, Self-Test, Cable Retention (Optional), Energy Saving Function |
IEC 62040-3 classification | VI-SS-211 |
BATTERIES AND AUTONOMY |
Batteries | 2x 12.0V/9.0Ah |
DC Voltage | 2x 12.0V |
Recharge Time | 4h to 90% |
Full Load Backup Time [min] | 2.0 |
Half Load Backup Time [min] | 8.0 |
Charger | 1 – 6A [1A] |
COMMUNICATION |
Communication | USB Type B – for Monitoring Software, RS-232, Management Card Slot |
Software | PowerMaster |
ENVIRONMENT |
Noise Level | < 40dB |
Fan Logic | Fan Off: Line Mode Fan On: Battery Mode, AVR ON, Battery Charging |
Temperature | 0°C – 40°C |
Humidity | 5% – 90% RH (non-condensing) |
IP | IP 20 |
LOGISTICS |
Manual Languages | DE, PL, FR, ES, EN |
EAN | 4260074983784 |
Product Dimensions (DxWxH) [mm] | 430 x 438 x 88 mm |
Product Weight [kg] | 15.9 |
Package Dimensions (DxWxH) [mm] | 550 x 556 x 231 mm |
Package Weight [kg] | 18.0 |
Pcs. per Outer Carton | 1 |